Exciter Model: EX2000
Following checks and corrections are applied during Validation and AutoCorrection.
- If 0.0 < Tr < 0.25*Mult*TimeStep then Tr = 0.0
ElseIf 0.25*Mult*TimeStep < Tr < 0.5*Mult*TimeStep then Tr = 0.5*Mult*TimeStep - If 0 < Te < Mult*TimeStep then Te = Mult*TimeStep
- If Vrmax < Vrmin then swap the values
- If Vamax < Vamin then swap the values
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Following treatment is handled during the transient numerical simulation
- If Vr > Vrmax, then Vrmax = Vr or if Vr < Vrmin, then Vrmin = Vr
- If Va > Vamax, then Vamax = Va or if Va < Vamin, then Vamin = Va
- If RefLimP > Vref, then RefLimP = Vref
- If Vfemax > Vemax, then Vfemax = Vemax
Model Equations and/or Block Diagrams
Parameters:
| FCL | Field Current Limit: 0=excluded, 1=included |
| MinGate2 | Minimum gate 2: 0=excluded, 1=included |
| Kpr | Proportional gain, pu |
| Kir | Integral gain, pu |
| Vrmax | Maximum exciter control signal, pu |
| Vrmin | Minimum exciter control signal, pu |
| Kpa | Amplifier proportional gain, pu |
| Kia | Amplifier integral gain, pu |
| VaMax | Maximum control element output, pu |
| VaMin | Minimum control element output, pu |
| Kp | Potential source gain, pu |
| Kl | Exciter field current limiter gain, pu |
| Te | Exciter field time constant, sec |
| Vfemax | Exciter field current limit parameter, pu |
| Ke | Exciter field resistance constant, pu |
| Kc | Rectifier loading factor proportional to commutating reactance |
| Kd | Exciter internal reactance, pu |
| KF1 | Feedback gain KF1 |
| KF2 | Feedback gain KF2 |
| E1 | Field voltage value, 1 |
| SE1 | Saturation factor at E1 |
| E2 | Field voltage value, 2 |
| SE2 | Saturation factor at E2 |
| Kvhz | Volt/hz gain |
| Krcc | Volt/reactive current gain |
| Tr | Filter time constant, sec |
| Ifdref1 | Field current first reference |
| Ifdref2 | Field current second reference |
| Ifdref3 | Field current third reference |
| Ifdref4 | Field current fourth reference |
| I1 | Inverse timing constant |
| T1 | Inverse timing current constant, sec |
| I2 | Inverse timing constant |
| T2 | Inverse timing current constant, sec |
| I3 | Inverse timing constant |
| T3 | Inverse timing current constant, sec |
| I4 | Inverse timing constant |
| T4 | Inverse timing current constant, sec |
| Tlead | Field current limiter time constant |
| Tlag | Field current limiter time constant |
| Kpifd | Proportional gain |
| Kiifd | Integral gain |
| IfdLimP | Maximum output |
| IfdLimN | Minimum output |
| IfdadVlim | Advance field current limit |
| Vemin | Minimimum exciter output voltage, pu |
| Reflimp | Voltage reference signal limit |